DocumentCode
2564305
Title
Open conductor detector system
Author
Westrom, A.C. ; Cokkinides, G.J. ; MelioPoulos, A. P Sakis ; Ayoub, A.H.
Author_Institution
Kearney Co., Altanta, GA, USA
fYear
1991
fDate
22-27 Sep 1991
Firstpage
392
Lastpage
399
Abstract
An open phase conductor detector system is described consisting of one or more transmitters and a receiver which communicate through the distribution line neutral conductor. The transmitter(s) detects the open phase conductor by monitoring the phase conductor voltage using redundant inputs. When an open phase conductor is detected, the transmitter injects a signal to the distribution line neutral conductor by means of a coupling current transformer (CT). The signal is frequency and duration coded. The receiver decodes the signal and generates a trip signal which may activate a breaker, a ground switch, or a recloser causing isolation of the distribution line with the open (downed) phase conductor. The system is presently implemented for single distribution lines. A prototype open conductor detector system has been constructed and field tested on a Georgia Power Company distribution system
Keywords
conductors (electric); current transformers; power cables; voltage measurement; Georgia Power Company; breaker; coupling current transformer; distribution line neutral conductor; duration coding; frequency coding; ground switch; open phase conductor detector system; phase conductor voltage; receiver; recloser; redundant inputs; transmitters; trip signal; Conductors; Current transformers; Decoding; Detectors; Frequency; Monitoring; Phase detection; Signal generators; Switches; Transmitters;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
Conference_Location
Dallas, TX
Print_ISBN
0-7803-0219-2
Type
conf
DOI
10.1109/TDC.1991.169536
Filename
169536
Link To Document