DocumentCode
2566405
Title
Application of GUPFC in China´s Sichuan power grid - modeling, control strategy and case study
Author
Sun, Lin ; Mei, Shengwei ; Lu, Qiang ; Ma, Jin
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume
1
fYear
2003
fDate
13-17 July 2003
Firstpage
175
Abstract
Installation of the four-converter generalized unified power flow controller (GUPFC) has been scheduled in Sichuan power grid. As a long-distance transmission system, Sichuan system has an undesirable power flow distribution, which has seriously infringed on its security. In this paper, a novel control law for the four-converter GUPFC has been proposed, which not only realizes the desired power flow distribution in Sichuan power gird, but also the voltage control of a substation. Furthermore, based completely on the locally measurable variables, the proposed controller could be very practical. Simulation studies have verified the effectiveness of the proposed controller. Compared with the conventional application of the UPFC, the GUPFC under the proposed controllers have shown great advantages and a very promising future.
Keywords
load flow control; power convertors; power distribution control; power system transient stability; power transmission control; Sichuan power grid; four-converter generalized unified power flow controller; power control; power flow distribution; transient stability; transmission system; Amplitude modulation; Computer aided software engineering; Impedance; Load flow; Power grids; Reactive power; Shunt (electrical); Substations; Sun; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2003, IEEE