DocumentCode
2566934
Title
Relocation of SVC from Shin-Shinano substation to Suruga substation
Author
Takeda, H. ; Shimada, K. ; Moriura, Y. ; Muramatsu, S. ; Pape, R.A.
Author_Institution
TM T&D Corp., Tokyo, Japan
Volume
1
fYear
2003
fDate
13-17 July 2003
Firstpage
357
Abstract
This paper reports on the successful relocation and reconstruction of an existing static Var compensator (SVC). In 1987, for experimental test purposes, an SVC with a controlled rating of 100 MVAr was installed in the Shin-Shinano 50 Hz-60 Hz frequency converter (FC) substation, on the 50 Hz, 500 kV side, to help control the voltage of the transmission network. Certain components of this test SVC were removed from service and returned to the factory to customize the design to meet the requirements of a new application, and to update and modify the equipment to meet the latest commercial operating requirements. This reconstructed SVC was installed in the Suruga substation, on the 154 kV side. In 2001, the SVC was successfully tested to verify its correct operation and application.
Keywords
frequency convertors; power transmission control; static VAr compensators; substations; voltage control; 100 MVAr; 154 kV; 50 to 60 Hz; 500 kV; SVC relocation; Shin-Shinano frequency converter substation; Suruga substation; commercial operating requirements; refurbishment; static Var compensator; transmission network; Bidirectional control; Control systems; Costs; Frequency conversion; Production facilities; Protection; Static VAr compensators; Substations; System testing; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2003, IEEE
Print_ISBN
0-7803-7989-6
Type
conf
DOI
10.1109/PES.2003.1267197
Filename
1267197
Link To Document