Magnification of transient voltages in multi-voltage-level, shunt-capacitor-compensated circuits
Author
Dunsmore, Dawn M. ; Taylor, Edgar R. ; Wirtz, Bernard F. ; Yanchula, T.L.
Author_Institution
ABB Power Systems Inc., Pittsburgh, PA, USA
fYear
1991
fDate
22-27 Sep 1991
Firstpage
898
Lastpage
907
Abstract
The transient response of two, three, and four series L - C loop systems is examined. The results of a case study of voltage magnification on an actual system with shunt capacitors at four different voltage levels are presented. On this system, equipment damage occurred within an industrial plant in the same time frame of the energization of a capacitor bank in a utility substation. Curves which illustrate the theoretical maximum components of the transient overvoltages and their interaction with the 60 Hz fundamental voltage in actual systems are presented
Keywords
capacitor storage; overvoltage; substations; transients; 60 Hz; L-C loop systems; capacitor bank; industrial plant; multi-voltage-level circuits; overvoltages; shunt-capacitor-compensated circuits; transient voltages; utility substation; Capacitors; Circuits; EMTP; Industrial plants; Industrial power systems; Power system transients; Substations; Surges; Transient analysis; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
Conference_Location
Dallas, TX
Print_ISBN
0-7803-0219-2
Type
conf
DOI
10.1109/TDC.1991.169610
Filename
169610
Link To Document