    Use of airside economizer for data center thermal management

  • Author

    Anubhav, K. ; Yogendra, J.

  • Author_Institution
    John F. Welch Technol. Center, GEITC, Bangalore, India
  • fYear
    2008
  • fDate
    17-20 Dec. 2008
  • Firstpage
    115
  • Lastpage
    124
  • Abstract
    Full-scale model of a representative data center was developed, with the arrangement of bringing outside air under suitable conditions. Four different world cities were considered to evaluate the energy savings over the entire year. Results show a significant saving in chiller energy (up to 70%), and even the possibility of switching off chillers for certain months of the year. The details of relative humidity and temperature variation inside the data center space and humidification/dehumidification requirements were investigated. The rack exit air temperature was found to be lower when economizer was used, as compared to the exit air temperature without the economizer. The lower exit air temperature results from reduced hot air recirculation, as the hot air is exhausted from the hot air outlet and fresh air is brought from the outside into the data center space. The saving in energy is significant and justifies the infrastructure improvements, such as improved filters and control mechanism for the outside air influx. Fan power to bring outside air into the data center space has also been investigated.
  • Keywords
    air conditioning; computer centres; fans; temperature control; air conditioning; air influx; air recirculation; airside economizer; chiller energy; data center; energy savings; exit air temperature; fan power; relative humidity; temperature variation; thermal management; Cooling; Humidity; Kinetic energy; Power system management; Temperature sensors; Thermal conductivity; Thermal engineering; Thermal expansion; Thermal management; Viscosity;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Thermal Issues in Emerging Technologies, 2008. ThETA '08. Second International Conference on
  • Conference_Location
    Cairo
  • Print_ISBN
    978-1-4244-3576-0
  • Type

    conf

  • DOI
    10.1109/THETA.2008.5167163
  • Filename
    5167163