• DocumentCode
    2584297
  • Title

    Application of Modern Relays to Dual-Breaker Line Terminals

  • Author

    Kasztenny, B. ; Voloh, I.

  • fYear
    2007
  • fDate
    27-29 March 2007
  • Firstpage
    35
  • Lastpage
    62
  • Abstract
    This paper discusses several protection and control aspects in relation to dual-breaker line terminals. First, breaker failure and reclosing functions are discussed as applied to dual-breaker configurations. Second, the paper talks about protection security as related to saturation of current transformers (CTs) under fault currents flowing locally through the two breakers. New generation of microprocessor-based line relays support dual CT inputs to monitor both breakers individually, and three voltage points to provide for the main line protection, and synchrocheck across both breakers. The paper points to advantages and disadvantages of integration protection, and provides some guidance regarding dual-breaker line applications
  • Keywords
    circuit breakers; current transformers; failure analysis; fault currents; microprocessor chips; relay protection; switchgear protection; breaker failure; current transformer saturation; dual-breaker line terminals; fault currents; microprocessor-based line relays; reclosing functions; synchrocheck; Condition monitoring; Current transformers; Fault currents; Feeds; Protection; Protective relaying; Relays; Security; Stability; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Protective Relay Engineers, 2007. 60th Annual Conference for
  • Conference_Location
    College Station, TX
  • Print_ISBN
    1-4244-0994-2
  • Electronic_ISBN
    1-4244-0995-0
  • Type

    conf

  • DOI
    10.1109/CPRE.2007.359890
  • Filename
    4201085