• DocumentCode
    2586142
  • Title

    Physical experiments on a ±10 kVAr STATCOM model

  • Author

    Li, Chun ; Wang, Zhonghong ; Ma, Xiaojun ; Lincheng Xiu

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • Volume
    2
  • fYear
    1999
  • fDate
    31 Jan-4 Feb 1999
  • Firstpage
    1184
  • Abstract
    This paper presents the results of physical experiments on a ±10 kVAr STATCOM model developed by Tsinghua University of China, which is the prototype of a ±20 MVAr STATCOM to be commissioned in the Henan province of China. A series of physical experiments, including open/closed loop step response, pulse-blocking under severe disturbances, voltage regulation improvement, voltage stabilization under surge loads, power system stability limits enhancement and damping improvement of power swings, were performed on the model to simulate the performance of the STATCOM in a real power system. The conclusions derived in the laboratory are expected to be helpful to the operation of the ±20 MVAr STATCOM in the near future.
  • Keywords
    DC-AC power convertors; flexible AC transmission systems; invertors; power system stability; power transmission control; static VAr compensators; thyristor convertors; voltage control; 10 kVAr; FACTS; STATCOM; VSI; open/closed loop step response; performance testing; physical experiments; power swings damping; power system stability limits; pulse-blocking; severe disturbances; static VAr compensation; surge loads; voltage regulation improvement; voltage stabilization; Automatic voltage control; Damping; Laboratories; Power system modeling; Power system simulation; Power system stability; Prototypes; Pulse power systems; Surges; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society 1999 Winter Meeting, IEEE
  • Print_ISBN
    0-7803-4893-1
  • Type

    conf

  • DOI
    10.1109/PESW.1999.747376
  • Filename