• DocumentCode
    2592309
  • Title

    Transformer modeling as applied to differential protection

  • Author

    Guzmán, Armando ; Hou, Daqing ; Zocholl, Stanley E.

  • Author_Institution
    Schweitzer Eng. Labs. Inc., Pullman, WA, USA
  • Volume
    1
  • fYear
    1996
  • fDate
    26-29 May 1996
  • Firstpage
    108
  • Abstract
    This paper presents a power transformer model to evaluate differential element performance. The paper analyzes transformer energization, overexcitation, external fault and internal fault conditions with this model. Test results with an actual transformer validate the model. The paper includes a guide for properly selecting current transformers for differential protection applications. Accurate power transformer modeling and proper current transformer selection leads to improved transformer protection
  • Keywords
    current transformers; electrical faults; power transformer protection; power transformer testing; transformer windings; applications; current transformer; differential element performance evaluation; differential protection; energization; external faults; internal faults; overexcitation; power transformer model; selection guidelines; transformer test results; Artificial intelligence; Circuit faults; Current transformers; Inductance; Phase transformers; Power transformers; Protection; Protective relaying; Testing; Transformer cores;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Computer Engineering, 1996. Canadian Conference on
  • Conference_Location
    Calgary, Alta.
  • ISSN
    0840-7789
  • Print_ISBN
    0-7803-3143-5
  • Type

    conf

  • DOI
    10.1109/CCECE.1996.548050
  • Filename
    548050