• DocumentCode
    2622804
  • Title

    Currents closing via the copper ribbon of MV cables at single-phase short-circuits on the HV side of a 110/20 kV station

  • Author

    Toader, D. ; Haragus, St ; Blaj, C.

  • Author_Institution
    Dept. of Phys. Fundamentals of Eng., Univ. Politeh. of Timisoara, Timisoara
  • fYear
    2008
  • fDate
    22-24 May 2008
  • Firstpage
    191
  • Lastpage
    196
  • Abstract
    At a single-phase short-circuit on the 110 kV side of the transformer station the value of the current closing through the equivalent grounding electrode of the city or the industrial plant depends, to a great extent, on the position of the electrode relative to the 110 kV line which feed the fault. In the paper the influence of some parameters which affect the value of the short-circuit current which closes through the copper ribbon of the medium voltage cable is analyzed. The conditions in which this current has a maximum, respectively a minimum, are also investigated.
  • Keywords
    copper; power cables; power transformers; short-circuit currents; transformer substations; MV cables; copper ribbon; current closing; grounding electrode; industrial plant; medium voltage cable; short-circuit current; single-phase short-circuits; transformer station; voltage 110 kV; voltage 20 kV; Cables; Cities and towns; Conductors; Copper; Electrodes; Equations; Grounding; Impedance; Industrial plants; Medium voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Optimization of Electrical and Electronic Equipment, 2008. OPTIM 2008. 11th International Conference on
  • Conference_Location
    Brasov
  • Print_ISBN
    978-1-4244-1544-1
  • Electronic_ISBN
    978-1-4244-1545-8
  • Type

    conf

  • DOI
    10.1109/OPTIM.2008.4602365
  • Filename