• DocumentCode
    2624661
  • Title

    Two techniques in comparison for UPS´s low generation of harmonic currents in the network

  • Author

    Bertoneri, M. ; Freri, G. ; Gregorio, De

  • Author_Institution
    Borri SpA, Bibbiena, Italy
  • fYear
    1989
  • fDate
    15-18 Oct 1989
  • Abstract
    The solutions to the problem of sinusoidal wave distortion caused by voltage and current harmonics are described for two families of currently mass-produced uninterruptible power supply (UPS) systems. The first UPS range is three-phase from 10 to 300 kVA, realized by a fully controlled thyristor bridge where the generated harmonics distortion reduction is obtained by means of standard filters. The second range of products, manufactured for telecommunication, is single-phase up to 20 kVA and is realized by a high-current frequency chopper at sinusoidal current. This solution yields a distortion in the range of 3% and a PF of 0.99
  • Keywords
    choppers (circuits); harmonics; telecommunication equipment; thyristor applications; uninterruptible power supplies; 10 to 300 kVA; UPS; filters; harmonics; high-current frequency chopper; single-phase; sinusoidal wave distortion; telecommunication; three-phase; thyristor bridge; Bridge circuits; Frequency; Harmonic distortion; Manufacturing; Power harmonic filters; Power system harmonics; Telecommunication control; Thyristors; Uninterruptible power systems; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1989. INTELEC '89. Conference Proceedings., Eleventh International
  • Conference_Location
    Florence
  • Type

    conf

  • DOI
    10.1109/INTLEC.1989.88366
  • Filename
    88366