    Effects of switch mode power supply harmonic currents on building power systems and stand-by engine alternators

  • Author

    Plow, Robert

  • Author_Institution
    Lorain Products, Lorain, OH, USA
  • fYear
    1994
  • fDate
    30 Oct-3 Nov 1994
  • Firstpage
    665
  • Lastpage
    668
  • Abstract
    Power supplies drawing high peak currents are very common in today´s buildings. These high peak currents contain the odd harmonics, and of special interest are the triplen harmonics-3, 9, 15, etc. Small power supplies are commonly connected from phase to neutral of the typical building power system. Engineers commonly distribute the loads among the phases to balance the building loads. However, they often over-look the effects of the third order harmonics on neutral current, expecting the phase currents to partially cancel in the neutral. The third order harmonics add and can lead to very high neutral currents. The high currents may cause excessive heating in the neutral conductor. In addition the high peak currents can have an adverse effect on the output wave shape of stand-by engine alternators
  • Keywords
    alternators; building wiring; load distribution; power system harmonics; switched mode power supplies; building power systems; harmonic currents; load distribution; neutral current; output wave shape; phase currents; phase to neutral connection; stand-by engine alternators; switch mode power supply; triplen harmonics; Conductors; Current supplies; Engineering drawings; Heating; Power engineering and energy; Power supplies; Power system harmonics; Shape; Switches; Systems engineering and theory;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1994. INTELEC '94., 16th International
  • Conference_Location
    Vancouver, BC
  • Print_ISBN
    0-7803-2034-4
  • Type

    conf

  • DOI
    10.1109/INTLEC.1994.396580
  • Filename
    396580