• DocumentCode
    2669581
  • Title

    Study on the boiler drum water level based on Fuzzy adaptive control

  • Author

    Jing, Hulin ; Zhang Ke ; Tao, Liu

  • Author_Institution
    Electr. Power Coll., Inner Mongolia Univ. of Technol., Hohhot, China
  • fYear
    2012
  • fDate
    23-25 May 2012
  • Firstpage
    1659
  • Lastpage
    1663
  • Abstract
    The boiler control is the thermal power plant most basic industrial control. The cascade-three parameters water level control system includes steam drum water level, steam flow and water supply, adjust water supply for the opening, Fuzzy adaptive control by seeking the three parameters of PID controller and the relationship between e and ec, make the best adjustment for PID parameters on the steam drum water level system automatically. The simulation results show the system is more stable, can meet the load, volatile, and frequent fluctuations of water supply pressure, and improve the quality control of the internal and external disturbances.
  • Keywords
    adaptive control; boilers; fuzzy control; level control; three-term control; PID controller; boiler control; boiler drum water level; cascade-three parameters water level control system; fuzzy adaptive control; industrial control; quality control; steam drum water level system; water supply; Adaptive systems; Boilers; Power generation; Production; Regulators; Tuning; PID parameter; boiler drum water level; fuzzy adaptive;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Control and Decision Conference (CCDC), 2012 24th Chinese
  • Conference_Location
    Taiyuan
  • Print_ISBN
    978-1-4577-2073-4
  • Type

    conf

  • DOI
    10.1109/CCDC.2012.6244265
  • Filename
    6244265