• DocumentCode
    2671991
  • Title

    Major factors affecting cable ampacity

  • Author

    De León, Francisco

  • Author_Institution
    CYME Int. T&D, Que.
  • fYear
    0
  • fDate
    0-0 0
  • Abstract
    This paper presents a parametric study of the major factors affecting cable ampacity calculations. The current carrying capacity (or ampacity) of a cable depends on many of the installation properties and conditions. In this paper the effects on ampacity of conductor size, ambient temperature, bonding arrangement, duct size, soil thermal resistivity, resistivity and size of backfill (or duct bank) and depth of installation for underground installations are presented. For cables air the effects on ampacity of the intensity of solar radiation, the spacing from the wall and the grouping of cables are analyzed. For riser pole installations the effect of the solar radiation, wind speed, ventilation and diameter of the duct are shown
  • Keywords
    installation; materials properties; power cables; ambient temperature; backfill resistivity; backfill size; bonding arrangement; cable ampacity; cables grouping; conductor size; current carrying capacity; duct diameter; duct size; installation depth; installation properties; riser pole installations; soil thermal resistivity; solar radiation; underground installations; ventilation; wall spacing; wind speed; Bonding; Cables; Conductors; Ducts; Parametric study; Soil; Solar radiation; Temperature; Thermal conductivity; Thermal resistance; Ampacity; CYMCAP; Cable Rating; Cables in Air; Cables in Riser Poles; IEC Standards; Neher-McGrath; Underground Cables;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2006. IEEE
  • Conference_Location
    Montreal, Que.
  • Print_ISBN
    1-4244-0493-2
  • Type

    conf

  • DOI
    10.1109/PES.2006.1708875
  • Filename
    1708875