DocumentCode
2684663
Title
Prediction method for preventing reclosing on permanent fault of shunt compensated EHV/UHV transmission lines
Author
Zengping, Wang ; Haofang, Liu ; Yan, Xu ; Jing, Ma ; Junling, Liu
Author_Institution
Key Lab. of Power Syst. Protection, North China Electr. Power Univ., Baoding
fYear
0
fDate
0-0 0
Abstract
A criterion is proposed to distinguish between temporary and permanent faults of shunt compensated EHV/UHV transmission lines. Its compensation criterion is established. In order to improve its sensitivity when resonant frequency is high. The performance of the criterion and its compensation criterion is hardly influenced by fault distance, fault earth resistance and the currents of healthy phases. The criterion and its compensation criterion can distinguish between temporary and permanent faults effectively and quickly. Simulation tests show that the conclusions in this paper are correct
Keywords
fault currents; power transmission faults; prediction theory; fault currents; fault distance; fault earth resistance; permanent fault; prediction method; resonant frequency; sensitivity improvement; shunt compensated EHV-UHV transmission lines; Capacitance; Inductors; Power system stability; Power transmission lines; Prediction methods; Resonance; Resonant frequency; Shunt (electrical); Transmission lines; Voltage; permanent fault; power frequency component; resonant component; resonant frequency; shunt compensated EHV/UHV transmission lines; single-phase reclosing; temporary fault;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2006. IEEE
Conference_Location
Montreal, Que.
Print_ISBN
1-4244-0493-2
Type
conf
DOI
10.1109/PES.2006.1709611
Filename
1709611
Link To Document