  • Title

    The Characteristic Analysis of Grid Frequency Variation under Islanding Mode for Utility Interactive PV System with Reactive Power Variation Scheme for Anti-Islanding

  • Author

    Gyu-Ha Choe ; Hong-Sung Kim ; Han-Goo Kim ; Young-Ho Choi ; Jae-Chul Kim

  • Author_Institution
    Dept. of Electr. Eng., Kon-Kuk Univ., Seoul
  • fYear
    2006
  • fDate
    18-22 June 2006
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    To detect islanding mode when the grid is being tripped is a major safety issue in the grid connected PV system. And one of the widely used techniques to detect islanding mode is reactive power variation (RPV)method. In this paper, analytical design method is suggested for RPV method under IEEE recommended islanding test condition. And in order to show the validity of proposed method, EMTP based simulation was done for PV system with RPV method. Results shows proposed method is very useful
  • Keywords
    distributed power generation; photovoltaic power systems; power grids; reactive power; antiislanding; grid connected PV system; grid frequency variation; islanding mode detection; reactive power variation method; utility interactive PV system; Control systems; Frequency; Phase detection; Pulse width modulation; Reactive power; Safety; Signal generators; Testing; Virtual manufacturing; Voltage control;