DocumentCode
2712555
Title
Optimized Main Protection Scheme Design of 600MW Hydro Generator in Pubugou Power Station
Author
Xia, Yongjun ; Yin, Xianggen ; Chen, Deshu ; Zhang, Zhe ; Chen, Wei
Author_Institution
Huazhong Univ. of Sci. & Technol., Hubei
Volume
3
fYear
2006
fDate
6-8 Sept. 2006
Firstpage
871
Lastpage
875
Abstract
The paper analyzed all the possible faults that may happen in stator of Pubugou 600 MW multi-branch hydro generator. And transient electrical characteristics of these faults are simulated by simplified simulation model, which is constructed based on dual damper in each pole principle. Based on simulation data, the protection effects of different protection theories under different stator branch grouping modes on the neutral side are analyzed, and Pubugou generator optimized main protection scheme is proposed, which ensure the safety working for the generator and provide the references for the related engineering application and research work
Keywords
electrical safety; fault simulation; hydroelectric generators; hydroelectric power stations; machine protection; power generation faults; power generation protection; power system simulation; power system transients; stators; 600 MW; Pubugou power station; dual damper; engineering application; faults; multibranch hydro generator; neutral side; optimization; protection scheme; research work; safety working; simulation model; stator branch grouping modes; transient electrical characteristics; Analytical models; Damping; Data engineering; Design optimization; Electric variables; Power generation; Protection; Safety; Shock absorbers; Stators; Pubugou hydro-generator; internal fault; main protection scheme design; transient simulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference, 2006. UPEC '06. Proceedings of the 41st International
Conference_Location
Newcastle-upon-Tyne
Print_ISBN
978-186135-342-9
Type
conf
DOI
10.1109/UPEC.2006.367605
Filename
4218813
Link To Document