Abstract
Subsynchronous oscillation (SSO) in hybrid AC-DC power systems caused by highly non-linear HVDC devices can lead to shaft failure and electrical instability of a turbo-generator at oscillation frequencies lower than the normal system frequency. With more and more HVDC transmission systems installed in electrical power systems, analysis and control of such SSO becomes a great concern of power engineers in power system design and operations. In this paper, a sevennode hybrid AC-DC system with different operating modes is to be investigated where EMTDC/PSCAD based digital simulation system with detailed multi-block generator model and a HVDC transmission link based on the IEEE first benchmark system model is built to investigate the SSO caused by the HVDC link in a hybrid AC-DC power system. The impact of the HVDC system on damping the SSO will be presented. Also, some operating proposals aiming at damping or even eliminating the SSO in the hybrid AC-DC power system are presented and verified using digital simulations.
Keywords
HVDC power transmission; digital simulation; turbogenerators; EMTDC-PSCAD; HVDC transmission link; SSO; benchmark system model; damping; digital simulation system; electrical instability; hybrid AC-DC power system; multiblock generator model; oscillation frequency; power system design; subsynchronous oscillation; turbo-generator; HVDC system; Subsynchronous oscillation; hybrid AC-DC system;
fLanguage
English
Publisher
iet
Conference_Titel
AC and DC Power Transmission, 2010. ACDC. 9th IET International Conference on
Conference_Location
London
Type
conf
DOI
10.1049/cp.2010.1008
Filename
5728040
Link To Document