• DocumentCode
    2716049
  • Title

    High-speed transfer of two 4 KV motor bus sources using a digital motor bus transfer system

  • Author

    Orr, Gregory T. ; Cooper, Scott ; Mozina, Charles J.

  • Author_Institution
    Power Dept., Eastman Chem. Co., Kingsport, TN, USA
  • fYear
    2010
  • fDate
    9-13 May 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    At many industrial facilities, distribution busses serving critical loads are supplied from two power sources. Typically, this bus arrangement is in a main-tie-main arrangement. Upon the loss of the normal power source, critical motor loads must be transferred to the alternate source without damaging the equipment, and ideally, without interrupting the process. In this application, two digital motor bus transfer systems were installed to transfer two 4 KV busses to two sources. This paper describes the steps to applying a digital motor bus transfer system to medium-voltage switchgear at a large chemical company including the feasibility analysis, available transfer methods, input/output considerations, settings, and commissioning methods. A summary of actual operations data to date and lessons learned is also included.
  • Keywords
    Chemical analysis; Delay effects; Industrial plants; Medium voltage; Power engineering and energy; Production facilities; Substations; Switchgear; Systems engineering and theory; USA Councils; Automatic Bus Transfer; Transfer of Critical Loads;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial and Commercial Power Systems Technical Conference (I&CPS), 2010 IEEE
  • Conference_Location
    Tallahassee, FL, USA
  • Print_ISBN
    978-1-4244-5600-0
  • Type

    conf

  • DOI
    10.1109/ICPS.2010.5489883
  • Filename
    5489883