DocumentCode
2734324
Title
Switching transient analysis and specifications for practical hybrid high resistance grounded generator applications An IEEE/IAS Working Group report #2
Author
Shipp, David ; Pillai, Padmanabhan ; Bailey, B. ; Mozina, Charles ; Love, David ; Powell, Louie ; Nichols, Nicole ; Dionise, Thomas ; Locker, Tony ; Panetta, S. ; Wu, Aimin ; Hoerauf, Robert ; Paul, Deleglise ; Jones, Jessica R.
Author_Institution
Eaton Corp., Warrendale, PA, USA
fYear
2009
fDate
21-26 June 2009
Firstpage
181
Lastpage
189
Abstract
This paper reports on the continuing efforts of an IAS Working Group to investigate industry concerns with excessive stator fault-point burning damage in conjunction with various industrial generator grounding and ground fault protection practices. Previous working group efforts were reported in a series of papers discussing typical voltage bus connected industrial generator applications. These papers proposed a new method of grounding, called hybrid grounding, that offered the ability to limit damage while still providing the required level of ground fault current under all operating conditions. This new Working Group paper reports on the detail design requirements for hybrid grounding. The paper reports the results of switching transient studies that formed the bases for recommended over-voltage protection. It also provides guidance in selection of equipment and fault protection required for hybrid grounding. The experience gained with several hybrid grounding applications is also reported.
Keywords
earthing; electric generators; fault diagnosis; machine protection; switching transients; IAS Working Group; ground fault current; ground fault protection practices; hybrid grounding; industrial generator grounding; overvoltage protection; resistance grounded generator applications; stator fault-point burning damage; switching transient analysis; Circuit faults; Equations; Fault currents; Grounding; Hybrid power systems; Medium voltage; Protection; Stators; Switches; Transient analysis; ground fault protection; grounding; hybrid high resistance ground; medium voltage industrial generator;
fLanguage
English
Publisher
ieee
Conference_Titel
Pulp and Paper Industry Technical Conference, 2009. PPIC '09. Conference Record of 2009 Annual
Conference_Location
Birmingham, AL
ISSN
0190-2172
Print_ISBN
978-1-4244-3464-0
Electronic_ISBN
0190-2172
Type
conf
DOI
10.1109/PAPCON.2009.5185432
Filename
5185432
Link To Document