DocumentCode
2740229
Title
Time series index for GIS partial discharge detection
Author
Kuo, Cheng-Chien ; Chen, Hung-Cheng ; Chen, Chun-Te
Author_Institution
Dept. of Electr. Eng., St. John´´s Univ., Taipei, Taiwan
fYear
2011
fDate
1-4 Nov. 2011
Firstpage
364
Lastpage
367
Abstract
Partial discharge (PD) detection is an efficient diagnosis method to prevent the failure of electric equipments arising from degrading insulation. A recognition system by PD for Gas Insulated Switch (GIS) through acoustic emission with Time Series Index (TSI) is proposed. This paper provides a nondestructive and online partial discharge monitoring by acoustic emission technology. Through the provided TSI that can effectively distinguish noise from field measured signal, the detection of interior faults for GIS can then be achieved more accurately. The effectiveness and feasibility of the proposed approach were demonstrated by both of lab and field studies. Through the experiment and practical examples, they showed encouraging results suggesting that the proposed approach was capable of correctly determination of the state of internal partial discharge in GIS effectively.
Keywords
acoustic emission; gas insulated switchgear; partial discharge measurement; time series; GIS partial discharge detection; acoustic emission technology; electric equipments; gas insulated switch; time series index; Acoustic emission; Insulation; Lightning; Monitoring; Partial discharge measurement; Partial discharges; Time series analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning (APL), 2011 7th Asia-Pacific International Conference on
Conference_Location
Chengdu
Print_ISBN
978-1-4577-1467-2
Type
conf
DOI
10.1109/APL.2011.6110143
Filename
6110143
Link To Document