• DocumentCode
    2741844
  • Title

    Research on the inversion calculation method of overvoltage based on the nonlinear model of potential transformer

  • Author

    Yan, Lizhi ; Liang, Guishu ; Sun, Haifeng ; Liu, Xin ; Liu, Xixiao

  • Author_Institution
    Key Lab. of Power Equipments Defense of Hebei Province, North China Electr. Power Univ., Baoding, China
  • fYear
    2011
  • fDate
    1-4 Nov. 2011
  • Firstpage
    727
  • Lastpage
    730
  • Abstract
    Monitoring overvoltage is essential to the power system´s operating well. Potential transformer is an important measuring instrument in power station. Because of the high amplitude of lightning overvoltage and switching overvoltage, the iron core of potential transformer reaches saturation in a very short time. The iron core shows nonlinear characteristic, so the distortion of secondary voltage and current happens. This article uses a nonlinear model of 10kV potential transformer to restore the primary voltage from the secondary voltage by the inversion calculation.
  • Keywords
    lightning protection; overvoltage protection; potential transformers; power stations; power system measurement; inversion calculation method; iron core; lightning overvoltage amplitude; nonlinear model; overvoltage monitoring; potential transformer; power station measuring instrument; switching overvoltage; voltage 10 kV; Iron; Lightning; Switches; Transformer cores; Voltage control; Voltage measurement; Voltage transformers; inversion calculation; nonlinearities; overvoltage; potential transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Lightning (APL), 2011 7th Asia-Pacific International Conference on
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4577-1467-2
  • Type

    conf

  • DOI
    10.1109/APL.2011.6110222
  • Filename
    6110222