• DocumentCode
    2758198
  • Title

    Study of parameters influencing the performance of connectors used for load and temperature tests on transformers

  • Author

    Magdaleno-Adame, Salvador ; Fofana, I. ; Loiselle, L. ; Olivares-Galvan, J.C. ; Escarela-Perez, R. ; Georgilakis, P.S.

  • Author_Institution
    Inst. Tecnol. de Morelia, Morelia, Mexico
  • fYear
    2012
  • fDate
    10-13 June 2012
  • Firstpage
    311
  • Lastpage
    314
  • Abstract
    This paper emphasizes the factors to be considered when designing power connectors used in the load and temperature tests of power transformers. External conductors used to perform load and temperature tests in transformers are referred as power connectors in this contribution. Electrical and thermal investigations of a single-phase shell-type, 300 MVA, 400 kV-21.5 kV power transformer connector were performed. To analyze the behavior of the connector, a harmonic analysis to calculate losses by Joule effect generated in the electrical connector was first performed, followed by a thermal, finite element based analysis to determine temperature distribution. As heat sources, harmonic losses analyses were performed. Temperature distribution obtained by the finite element simulation was compared with measurements recorded by an infrared camera during the tests.
  • Keywords
    conductors (electric); electric connectors; finite element analysis; harmonic analysis; power transformer testing; temperature distribution; thermal analysis; Joule effect; apparent power 300 MVA; conductors; electrical connector; finite element analysis; finite element simulation; harmonic losses analysis; heat sources; infrared camera; load test; power transformer testing; single-phase shell-type power transformer connector; temperature distribution; temperature tests; thermal analysis; voltage 400 kV to 21.5 kV; Connectors; Contacts; Copper; Finite element methods; Power transformers; Temperature; Temperature measurement; Load test; contact area; electrical conector; finite element method; temperature test;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation (ISEI), Conference Record of the 2012 IEEE International Symposium on
  • Conference_Location
    San Juan, PR
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4673-0488-7
  • Electronic_ISBN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.2012.6251479
  • Filename
    6251479