Tripping Characteristics of Residual Current Devices under Non-Sinusoidal Currents
Author
Luo, Xiang ; Du, Y. ; Wong, X.H. ; Chen, M.L.
Author_Institution
Shanghai Jiao Tong Univ., Shanghai, China
fYear
2010
fDate
3-7 Oct. 2010
Firstpage
1
Lastpage
6
Abstract
This paper presented an experimental investigation into operating characteristics of RCDs under an unbalanced current. The unbalanced current included the harmonic current, ground fault current, and surge current. A testing system was first set up in the laboratory, and the minimum value of the current causing RCD samples to trip were recorded. To obtain consistent testing results, RCD samples under test were demagnetized prior to each test. It is found that RCD tripping is primarily determined by the peak value of the unbalanced current. Under a ground fault RCDs installed in healthy circuits may trip. It would be necessary to limit the maximum leakage current in the circuits to avoid such nuisance tripping. Under surge conditions RCDs could withstand a large short-duration current. However, a long-duration surge current can easily cause RCDs to trip.
Keywords
earthing; fault currents; residual current devices; RCD; ground fault current; harmonic current; maximum leakage current; nonsinusoidal currents; nuisance tripping; residual current devices; surge current; tripping characteristics; unbalanced current; Circuit faults; Current transformers; Fault currents; Harmonic analysis; Leakage current; Magnetic cores; Surges;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Society Annual Meeting (IAS), 2010 IEEE
Conference_Location
Houston, TX
ISSN
0197-2618
Print_ISBN
978-1-4244-6393-0
Type
conf
DOI
10.1109/IAS.2010.5616786
Filename
5616786
Link To Document