DocumentCode
2792121
Title
Electrical (AC) aging and growth of water trees in cross-linked polyethylene (XLPE) cables in humid environment
Author
Das-Gupta, D.K. ; Svatik, A. ; Cooper, D.E.
Author_Institution
Sch. of Electron. Eng. Sci., Univ. of Wales, Gwynedd, UK
fYear
1991
fDate
8-12 Jul 1991
Firstpage
139
Abstract
The electrical aging behavior of XLPE power distribution cables has been investigated after AC (6 kV/mm) aging in water at room temperature by several techniques, including thermally stimulated discharge current (TSDC) and thermal transient current (TTC), which appear to provide acceptable information on the polarization of the insulator. Water trees were not observed with these cables, AC aged for up to 1000 h
Keywords
ageing; cable insulation; cable testing; dielectric polarisation; electric breakdown of solids; insulation testing; materials testing; organic insulating materials; polymers; thermally stimulated currents; 1000 h; AC aging; TSDC; TTC; XLPE power distribution cables; aging in water; cross-linked polyethylene; electrical aging behavior; humid environment; insulator polarization; room temperature; thermal transient current; thermally stimulated discharge current; water trees; Aging; Cable insulation; Dielectric measurements; Dielectrics and electrical insulation; Electric variables measurement; Polarization; Polyethylene; Polymers; Power distribution; Trees - insulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
Conference_Location
Tokyo
Print_ISBN
0-87942-568-7
Type
conf
DOI
10.1109/ICPADM.1991.172033
Filename
172033