• DocumentCode
    280751
  • Title

    Pole mounted fault passage indicators

  • Author

    Newman, Trevor

  • fYear
    1990
  • fDate
    33015
  • Firstpage
    42552
  • Lastpage
    42553
  • Abstract
    Overhead lines are very susceptible to faults because of the exposure of the system equipment to the extremes of weather and environmental conditions. Fault finding on 11 kV overhead lines is often extremely time consuming due to the remote locations and difficulty of access for personnel. The author investigates pole mounted fault passage indicators (FPI). The FPI is mounted on the pole some distance below the conductors. When a change in status of the magnetic field radiating from the overhead line conductor, caused by a downstream faults, occurs the FPI is triggered. The indicator enables quick identification of the passage of the fault
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Improving Supply Security on 11 kV Overhead Networks, IEE Colloquium on
  • Conference_Location
    London
  • Type

    conf

  • Filename
    191160