• DocumentCode
    282720
  • Title

    Lightning protection of pole mounted transformers

  • Author

    Darveniza, M. ; Mercer, D.R.

  • Author_Institution
    Dept. of Electr. Eng., Queensland Univ., St. Lucia, Qld., Australia
  • fYear
    1989
  • fDate
    8-12 May 1989
  • Firstpage
    160
  • Abstract
    The authors review Australian experience with a system of overvoltage protection for distribution transformers, first implemented in 1965-6. The major reduction achieved in transformer failure rates is attributed to the relocation of HV arresters close to the terminals, and to the fitting of LV arresters. Previously unpublished data from more than 12 years of field experience supports this attribution, and confirms Australian and subsequent American and Norwegian laboratory studies. During the field programme, several thousands of arresters were recovered from service, and the results of post-recovery tests, and of examinations of dismantled components, were compared with their service history
  • Keywords
    distribution networks; lightning protection; overvoltage protection; power system protection; power transformers; transformer protection; Australia; arresters; failure rates; lightning protection; overvoltage protection; pole mounted transformers; post-recovery tests; power system transformer protection;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution, 1989. CIRED 1989. 10th International Conference on
  • Conference_Location
    Brighton
  • Print_ISBN
    0-85296-376-9
  • Type

    conf

  • Filename
    206060