• DocumentCode
    2833331
  • Title

    Taking account of harmonic currents in the selection of-busbar systems

  • Author

    Leprêtre, P. ; Mary, M. ; Schonek, I.

  • Author_Institution
    Switchboard & Busbar Syst. Div., Schneider-Electr., Montmelian, France
  • fYear
    2004
  • fDate
    12-15 Sept. 2004
  • Firstpage
    41
  • Lastpage
    45
  • Abstract
    Single-phase electronic loads in office buildings produce triplen harmonic currents which summate in the neutral conductor. The selection of busbar systems must take these currents into account. Through the use of theory and measurements, the understanding of heat circulation due to harmonic currents leads to a better knowledge of harmonic current carrying capability of busbar systems. As a result, the optimum current rating can be selected. A standard busbar system selected using this approach is a better solution than a 200% neutral with special construction.
  • Keywords
    busbars; conductors (electric); power system harmonics; busbar systems; heat circulation; neutral conductor; office buildings; optimum current rating; power system harmonics; single-phase electronic loads; triplen harmonic currents; Conductors; Current measurement; Fluorescent lamps; Induction generators; Power generation; Power system harmonics; Pulsed power supplies; Switches; Variable speed drives; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power, 2004. 11th International Conference on
  • Print_ISBN
    0-7803-8746-5
  • Type

    conf

  • DOI
    10.1109/ICHQP.2004.1409326
  • Filename
    1409326