DocumentCode
2833331
Title
Taking account of harmonic currents in the selection of-busbar systems
Author
Leprêtre, P. ; Mary, M. ; Schonek, I.
Author_Institution
Switchboard & Busbar Syst. Div., Schneider-Electr., Montmelian, France
fYear
2004
fDate
12-15 Sept. 2004
Firstpage
41
Lastpage
45
Abstract
Single-phase electronic loads in office buildings produce triplen harmonic currents which summate in the neutral conductor. The selection of busbar systems must take these currents into account. Through the use of theory and measurements, the understanding of heat circulation due to harmonic currents leads to a better knowledge of harmonic current carrying capability of busbar systems. As a result, the optimum current rating can be selected. A standard busbar system selected using this approach is a better solution than a 200% neutral with special construction.
Keywords
busbars; conductors (electric); power system harmonics; busbar systems; heat circulation; neutral conductor; office buildings; optimum current rating; power system harmonics; single-phase electronic loads; triplen harmonic currents; Conductors; Current measurement; Fluorescent lamps; Induction generators; Power generation; Power system harmonics; Pulsed power supplies; Switches; Variable speed drives; Voltage;