Abstract
A new relay has been developed jointly by Manweb and GEC-Alsthom, the microprocessor protection relay. The version suitable for overhead line protection is denoted as MPR(OLP). This has been designed to utilise rented low grade variable frequency (VF) pilots to perform a unit protection function. It has been found that rented communication circuits whether DC or VF may fail coincident with power system faults. The practice of having back up protection at the BSP only, causes too much disruption. For this reason a back up protection was designed and incorporated into MPR(OLP). The in-built back up protection is called voltage compensated protection. This is a new protection but it has evolved from overcurrent relay principles. It uses sequence voltages to modify an IDMT characteristic
Keywords
compensation; distribution networks; microcomputer applications; power overhead lines; power system computer control; power system protection; relay protection; back up protection; distribution networks; faults; microprocessor protection relay; overcurrent; power overhead lines; power system protection; sequence voltages; voltage compensated protection;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, 1993., Fifth International Conference on
Conference_Location
York
Print_ISBN
0-85296-559-1
Type
conf
Filename
224557
Link To Document