• DocumentCode
    2861705
  • Title

    Optimal control strategy for cascaded STATCOM under unsymmetrical power system conditions

  • Author

    Yuan, Zhichang ; Xia, Tao

  • Author_Institution
    Dept. of electrical engineering, Tsinghua university, Beijing, China
  • Volume
    4
  • fYear
    2012
  • fDate
    2-5 June 2012
  • Firstpage
    2721
  • Lastpage
    2726
  • Abstract
    This paper presents a optimal control method for cascaded STATCOM under unsymmetrical conditions by power faults. Cascaded H-bridge multilevel converter is considered suitable for power system application. Since unsymmetrical faults have much higher probability than symmetrical faults in power system, it is importance for STATCOM to operate continuously under unsymmetrical conditions. While isolated capacitors in each H-bridge makes it more difficult to balancing 3-phase dc voltage. The mathematical model of cascaded STATCOM and its operation principle under unsymmetrical power conditions are analyzed. A optimal control method based on energy balance of 3-phase dc capacitors, including selection method of 3-phase current reference to ensure dc voltage stability and continuous operation. The validity is examined by digital simulation under ±50Mvar cascaded STATCOM connected to 110kV power grid.
  • Keywords
    Automatic voltage control; Capacitors; Equations; Mathematical model; Optimal control; Power system stability; Cascaded STATCOM; optimal control strategy; unsymmetrical power conditions;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics and Motion Control Conference (IPEMC), 2012 7th International
  • Conference_Location
    Harbin, China
  • Print_ISBN
    978-1-4577-2085-7
  • Type

    conf

  • DOI
    10.1109/IPEMC.2012.6259293
  • Filename
    6259293