• DocumentCode
    2896517
  • Title

    Integration of imaging pyrometry into the Wampum Plant automation project [cement plant]

  • Author

    Petrus, Carl R.

  • Author_Institution
    Medusa Cement, Wampum, PA, USA
  • fYear
    1997
  • fDate
    20-24 Apr 1997
  • Firstpage
    419
  • Lastpage
    431
  • Abstract
    The measurement of the flame temperature and burning zone conditions in cement kilns has long been considered absolutely critical in maintaining optimum clinker production levels. This process control has evolved over the years; from the well-trained eye of a seasoned kiln burner to the dual imaging pyrometry technology used to continually monitor cement kiln burning zones. This device easily integrates into any of today´s sophisticated control systems, and quickly becomes a critical link in establishing a control strategy for kiln operation. This paper spotlights the installation and operation of three Spyrometer TM systems at Medusa´s Wampum facility (USA) during the plant´s 1995 automation project. The camera´s microprocessors link directly to the remote I/O racks of the new PLC-based control system. So they not only provide a continual window into all three burning zones, but they monitor six temperatures at operator specified windows. These inputs can also be used as a BIF regulated waste fuel interlock or as an expert system control parameter. The data generated from the pyrometer´s temperature measurement can also be used in an effective clinker quality control program. By coupling clinker microscopy and cement physical testing with the trended data, tangible performance improvements are demonstrated for not only the product, but with the process operation
  • Keywords
    cement industry; control systems; expert systems; infrared imaging; process control; programmable controllers; project engineering; pyrometers; quality control; spectral methods of temperature measurement; BIF regulated waste fuel interlock; PLC-based control system; USA; burning zone conditions measurement; cement kilns; cement plant control; clinker quality control; expert system control parameter; flame temperature measurement; imaging pyrometry; microprocessors; performance improvements; remote I/O racks; Automatic control; Automation; Control systems; Fires; Kilns; Microprocessors; Process control; Production; Temperature measurement; Temperature sensors;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Cement Industry Technical Conference. 1997. XXXIX Conference Record., 1997 IEEE/PCA
  • Conference_Location
    Hershey, PA
  • ISSN
    1079-9931
  • Print_ISBN
    0-7803-3962-2
  • Type

    conf

  • DOI
    10.1109/CITCON.1997.599412
  • Filename
    599412