• DocumentCode
    2914061
  • Title

    Increase of current carrying ability of vacuum interrupter

  • Author

    Sato, Y. ; Arazoe, S. ; Okumo, H. ; Takao, N. ; Yanabu, S.

  • Author_Institution
    Tokyo Denki Univ., Tokyo, Japan
  • fYear
    2010
  • fDate
    Aug. 30 2010-Sept. 3 2010
  • Firstpage
    198
  • Lastpage
    201
  • Abstract
    Recently, as a substitute for SF6 gas circuit breaker, a vacuum circuit breaker with low environmental effect is attracting attention. The development of vacuum circuit breaker adapted high voltage and large current. Therefore, increase of current carrying ability is necessary for vacuum circuit breaker, and it may be possible to increase current carrying ability by the vacuum interrupters in parallel. Therefore, arc currents of vacuum interrupters in parallel are measured. In other application for nuclear experiment for large Tokomak Machine, interrupters in parallel is interrupted DC 130kA successfully and it may be also acceptable parallel operation of vacuum interrupter for the increase of interruption capacity.
  • Keywords
    SF6 insulation; vacuum circuit breakers; vacuum interrupters; SF6 gas circuit breaker; Tokomak Machine; current 130 kA; vacuum circuit breaker; vacuum interrupter; Circuit breakers; Electrodes; Interrupters; Magnetic fields; Spirals; Vacuum arcs; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum (ISDEIV), 2010 24th International Symposium on
  • Conference_Location
    Braunschweig
  • ISSN
    1093-2941
  • Print_ISBN
    978-1-4244-8367-9
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2010.5625834
  • Filename
    5625834