Title
Experiment Study on Tower Cooling Energy-Saving Technology
Author
Amin, Ji ; Li, He ; Zhiqiang, Yue ; Li, Jie ; Yin, Gang ; Qinggang, Zhang
Author_Institution
Haerbin Univ. of Commerce, Harbin, China
fYear
2011
fDate
19-20 Feb. 2011
Firstpage
728
Lastpage
730
Abstract
During the transition season periods the technology of tower cooling is used to cool the internal heat source region in the buildings, which is energy saving and environment-friendly technology. To aim at climatic conditions of the transition season in Harbin, The air conditioning experimental study is done through the technology of tower cooling directly. The annual service hours of tower cooling is attained, the influence factors of tower cooling and energy-saving effectiveness is analyzed. With the result from experiment, when wet bulb temperature 10°C outdoor is as diversion temperature, energy saving rate of the system can reach 14.8%.
Keywords
air conditioning; cooling towers; energy conservation; air conditioning; climatic conditions; internal heat source; temperature 10 C; tower cooling energy saving technology; wet bulb temperature; Buildings; Cooling; Heating; Poles and towers; Temperature distribution; Temperature measurement; energy saving; experiments; fluence factors; towers cooling;