• DocumentCode
    2923056
  • Title

    Statistical evaluation of optimum islanding preventing method for utility interactive small scale dispersed PV systems

  • Author

    Kobayashi, Hiromu ; Takigawa, Kiyoshi

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    1
  • fYear
    1994
  • fDate
    5-9 Dec 1994
  • Firstpage
    1085
  • Abstract
    The optimum islanding preventing method for the small scale dispersed PV system were evaluated, based on a simulation analysis concerning the occurrence probability of islanding phenomenon in actual operation. As a result, it is sufficient to adopt only one developed measure when the PV penetration ratio to distribution line capacity is less than 20% to 30%. It is necessary to adopt a combination method consisting of 2 or more developed measures when the penetration ratio is more than 40%. The harmonic monitoring method is effective in the case of using it in a combination method
  • Keywords
    photovoltaic power systems; power system harmonics; power system measurement; probability; simulation; PV penetration ratio; combination method; distribution line capacity; harmonic monitoring method; occurrence probability; optimum islanding prevention; probability; simulation analysis; small scale dispersed PV systems; statistical evaluation; utility interactive PV systems; Analytical models; Fault detection; Frequency measurement; Phase detection; Phase frequency detector; Phase measurement; Power measurement; Probability; Solar power generation; Time measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Photovoltaic Energy Conversion, 1994., Conference Record of the Twenty Fourth. IEEE Photovoltaic Specialists Conference - 1994, 1994 IEEE First World Conference on
  • Conference_Location
    Waikoloa, HI
  • Print_ISBN
    0-7803-1460-3
  • Type

    conf

  • DOI
    10.1109/WCPEC.1994.520150
  • Filename
    520150