• DocumentCode
    2929032
  • Title

    PD Detecting during the Growth of Electrical Trees in HV XLPE Cable

  • Author

    Sui, Heng ; Shen, LiMing ; Wang, Wei ; Yu, YanLong ; Wang, Zan ; Gao, ChaoFei

  • Author_Institution
    Beijing Key Lab. of High Voltage & EMC, North China Electr. Power Univ., Beijing, China
  • fYear
    2011
  • fDate
    25-28 March 2011
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Online observing the growth of electrical trees in XLPE cable section and monitoring its PD characteristics have been conducted. With different voltage levels, the electrical trees had different characteristics of growth. Secondary voltage applied promoted the growth of bush-like electrical trees. The PD data during the growth of electrical trees had been analyzed and found that the trends of the magnitude and times of PD in a frequency cycle with time are similar to the growth of bush-like electrical trees, which can be used to evaluate the degree of development of electrical trees in XLPE insulation, especially for HV and EHV cables.
  • Keywords
    XLPE insulation; partial discharges; power cable insulation; trees (electrical); HV XLPE cable; XLPE insulation; bush-like electrical trees; partial discharge detection; secondary voltage; Breakdown voltage; Cable insulation; Partial discharges; Power cables; Vegetation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
  • Conference_Location
    Wuhan
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4244-6253-7
  • Type

    conf

  • DOI
    10.1109/APPEEC.2011.5748496
  • Filename
    5748496