• DocumentCode
    2929269
  • Title

    Research on Fast Fault Isolation and Restoration for Distribution

  • Author

    Ma, Shicong ; Xu, Bingyin ; Deng, Feng ; Bo, Zhiqian

  • Author_Institution
    Alstom Grid, Stafford, UK
  • fYear
    2011
  • fDate
    25-28 March 2011
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    A new fault isolation and restoration technique for distribution automation, which employs local Ethernet network, is presented. It can isolate all short circuit faults in the loop within 300ms and restore the supply of healthy sections in less than 1.2 seconds. A reliable fault location method for isolating the single phase to ground fault in the non-effectively earthed network, which makes use of the fault generated transient signals is also proposed. The simulation and Laboratory test results show the proposed techniques are reliable and feasible.
  • Keywords
    power distribution faults; power engineering computing; Ethernet network; distribution automation; fault isolation; fault location method; fault restoration; short circuit faults; transient signals; Automation; Circuit faults; Ethernet networks; Fault diagnosis; Integrated circuit reliability; Switches; Transient analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
  • Conference_Location
    Wuhan
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4244-6253-7
  • Type

    conf

  • DOI
    10.1109/APPEEC.2011.5748508
  • Filename
    5748508