• DocumentCode
    2930302
  • Title

    An approach to diagnose pressure hazard of vacuum bulbs

  • Author

    Yamamoto, Osamu ; Naruse, Hiroki ; Morii, Hiroshi

  • Author_Institution
    Dept. of Electr. Eng., Kyoto Univ., Kyoto, Japan
  • fYear
    2011
  • fDate
    23-27 Oct. 2011
  • Firstpage
    249
  • Lastpage
    252
  • Abstract
    Vacuum bulbs may encounter the pressure rise hazard that results in failure in interrupting over currents in power systems. The pressure may unexpectedly increase due to a slow leak through cracks after a long period of operation in the power system. Several methods for monitoring the pressure onsite have been proposed so far, but most of them are poor in the ability to checkup the hazardous pressure level of 1 Pa or less. The present paper reports the results of a primitive attempt conducted for diagnostic purposes. In the study, by monitoring the electrification on the insulator surface of a real vacuum bulb, we successfully provide a method to detect the pressure rise around 10-1 Pa.
  • Keywords
    hazards; vacuum circuit breakers; vacuum interrupters; VCB; electrification monitoring; insulator surface; power systems; pressure 1 Pa; pressure hazard diagnosis; pressure monitoring; vacuum bulbs; vacuum circuit breakers; Anodes; Cathodes; Insulators; Monitoring; Power systems; Probes; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment - Switching Technology (ICEPE-ST), 2011 1st International Conference on
  • Conference_Location
    Xi´an
  • Print_ISBN
    978-1-4577-1273-9
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2011.6122981
  • Filename
    6122981