DocumentCode
2931255
Title
Finite element analysis of electric field of outdoor insulators under pollution un-uniform distribution
Author
Xu, Jianyuan ; Su, Wei ; Teng, Yun ; Lin, Xin
Author_Institution
Liaoning Province Key Lab. of Power Grid Safe Oper. & Monitoring, Shenyang Univ. of Technol., Shenyang, China
fYear
2011
fDate
23-27 Oct. 2011
Firstpage
462
Lastpage
465
Abstract
In order to study the effect of pollution un-uniform distribution on insulation performance of outdoor insulators, in the paper, the size of the dirt layer conductivity is used to describe the pollution extent of insulators and then the three-dimension harmonic quasi-static electric field of XP-160 insulators under pollution un-uniform distribution is calculated. The effects of different conductivity of dirt layers and several typical pollution un-uniform distributions to the electric field distribution along the surface of insulators are investigated. Comparing the leakage current obtained from artificial contamination test with the results of calculation, the reliability of the model is verified.
Keywords
finite element analysis; insulator contamination; leakage currents; dirt layer conductivity; electric field distribution; finite element analysis; leakage current; outdoor insulators; pollution un-uniform distribution; three-dimension harmonic quasistatic electric field; Electric fields; Finite element methods; Insulators; Leakage current; Pollution; Surface contamination;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Power Equipment - Switching Technology (ICEPE-ST), 2011 1st International Conference on
Conference_Location
Xi´an
Print_ISBN
978-1-4577-1273-9
Type
conf
DOI
10.1109/ICEPE-ST.2011.6123031
Filename
6123031