• DocumentCode
    2931255
  • Title

    Finite element analysis of electric field of outdoor insulators under pollution un-uniform distribution

  • Author

    Xu, Jianyuan ; Su, Wei ; Teng, Yun ; Lin, Xin

  • Author_Institution
    Liaoning Province Key Lab. of Power Grid Safe Oper. & Monitoring, Shenyang Univ. of Technol., Shenyang, China
  • fYear
    2011
  • fDate
    23-27 Oct. 2011
  • Firstpage
    462
  • Lastpage
    465
  • Abstract
    In order to study the effect of pollution un-uniform distribution on insulation performance of outdoor insulators, in the paper, the size of the dirt layer conductivity is used to describe the pollution extent of insulators and then the three-dimension harmonic quasi-static electric field of XP-160 insulators under pollution un-uniform distribution is calculated. The effects of different conductivity of dirt layers and several typical pollution un-uniform distributions to the electric field distribution along the surface of insulators are investigated. Comparing the leakage current obtained from artificial contamination test with the results of calculation, the reliability of the model is verified.
  • Keywords
    finite element analysis; insulator contamination; leakage currents; dirt layer conductivity; electric field distribution; finite element analysis; leakage current; outdoor insulators; pollution un-uniform distribution; three-dimension harmonic quasistatic electric field; Electric fields; Finite element methods; Insulators; Leakage current; Pollution; Surface contamination;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment - Switching Technology (ICEPE-ST), 2011 1st International Conference on
  • Conference_Location
    Xi´an
  • Print_ISBN
    978-1-4577-1273-9
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2011.6123031
  • Filename
    6123031