• DocumentCode
    2931759
  • Title

    Estimation of interruption performance in high-voltage circuit breakers with a modified method for arc parameter evaluation

  • Author

    Urai, Hajime ; Ooshita, Youichi ; Koizumi, Makoto ; Yaginuma, Noriyuki ; Tsukushi, Masanori

  • Author_Institution
    Hitachi Res. Lab., Ltd., Hitachi, Japan
  • fYear
    2011
  • fDate
    23-27 Oct. 2011
  • Firstpage
    559
  • Lastpage
    565
  • Abstract
    Interruption performance of high-voltage circuit breakers has been quantitatively evaluated through current zero measurements during interruption tests. The interruption capabilities of the circuit breakers are able to be estimated by means of an arc model calculation. The parameters of the arc model are determined through the current zero measurements. In order to simulate more precisely the success or failure of current interruption, a modified extraction method of arc parameters is proposed in this paper. The arc parameters are calculated by combining an equivalent circuit calculation and a non-linear least square fitting for current zero measurement data. The arc model calculation with the modified extraction method of arc parameters is applied to the development and design of an actual high-voltage circuit breaker. The capacitance required for 80 kA interruption can be estimated based on the current zero data measured during 50 kA interruption tests. The test results of interruption and failure agree well with the predicted performance. The proposed method consisting of the arc parameter extraction from current zero data and characterization of the parameters as the function of arc time constant can evaluate short-line fault interruption performance in high-voltage circuit breakers.
  • Keywords
    arcs (electric); circuit breakers; equivalent circuits; interrupters; least squares approximations; arc parameter evaluation; arc parameters; arc time constant; current 50 kA; current 80 kA; current interruption; current zero measurements; equivalent circuit; high-voltage circuit breakers; interruption tests; nonlinear least square fitting; short-line fault interruption; Current measurement; Fitting;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Equipment - Switching Technology (ICEPE-ST), 2011 1st International Conference on
  • Conference_Location
    Xi´an
  • Print_ISBN
    978-1-4577-1273-9
  • Type

    conf

  • DOI
    10.1109/ICEPE-ST.2011.6123053
  • Filename
    6123053