• DocumentCode
    2939412
  • Title

    Study on Detection of SF6 Gas Leakage Based on Photoacoustic Spectrometry

  • Author

    Xu, Yuanzhe ; Zhou, Hongjing ; Li, Bo ; Zhao, Xin

  • Author_Institution
    Sch. of Electr. Eng., Northeast Dianli Univ., Jilin, China
  • Volume
    1
  • fYear
    2009
  • fDate
    11-12 April 2009
  • Firstpage
    261
  • Lastpage
    265
  • Abstract
    In view of the problems of using traditional monitoring method for SF6 gas leakage in electrical equipments, according to the photoacoustic spectrometry technology, the photoacoustic spectrometry experiment system is designed for detecting SF6 gas concentration. The generation of photoacoustic spectrum is presented, the photoacoustic technique is used to survey the photoacoustic characteristic of SF6 molecule at 10.6 mum wavelength, resonance frequency of PA cell is determined. The detection sensitivity can reach 0.12times10-9 under standard atmospheric pressure. The results show that the system could detect the SF6 gas concentration accurately and reliably, it has a lot of advantages and the widespread application value and prospect.
  • Keywords
    discharges (electric); electrical faults; photoacoustic spectroscopy; SF6 gas concentration; SF6 gas leakage; SF6 molecule; electrical equipments; photoacoustic spectrometry; wavelength 10.6 mum; Corona; Gas insulation; Gases; Infrared detectors; Infrared imaging; Infrared spectra; Leak detection; Spectroscopy; Sulfur hexafluoride; Temperature; PA cell; SF6 gas; leakage detection; photoacoustic spectrometry;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Measuring Technology and Mechatronics Automation, 2009. ICMTMA '09. International Conference on
  • Conference_Location
    Zhangjiajie, Hunan
  • Print_ISBN
    978-0-7695-3583-8
  • Type

    conf

  • DOI
    10.1109/ICMTMA.2009.148
  • Filename
    5202962