DocumentCode
2939412
Title
Study on Detection of SF6 Gas Leakage Based on Photoacoustic Spectrometry
Author
Xu, Yuanzhe ; Zhou, Hongjing ; Li, Bo ; Zhao, Xin
Author_Institution
Sch. of Electr. Eng., Northeast Dianli Univ., Jilin, China
Volume
1
fYear
2009
fDate
11-12 April 2009
Firstpage
261
Lastpage
265
Abstract
In view of the problems of using traditional monitoring method for SF6 gas leakage in electrical equipments, according to the photoacoustic spectrometry technology, the photoacoustic spectrometry experiment system is designed for detecting SF6 gas concentration. The generation of photoacoustic spectrum is presented, the photoacoustic technique is used to survey the photoacoustic characteristic of SF6 molecule at 10.6 mum wavelength, resonance frequency of PA cell is determined. The detection sensitivity can reach 0.12times10-9 under standard atmospheric pressure. The results show that the system could detect the SF6 gas concentration accurately and reliably, it has a lot of advantages and the widespread application value and prospect.
Keywords
discharges (electric); electrical faults; photoacoustic spectroscopy; SF6 gas concentration; SF6 gas leakage; SF6 molecule; electrical equipments; photoacoustic spectrometry; wavelength 10.6 mum; Corona; Gas insulation; Gases; Infrared detectors; Infrared imaging; Infrared spectra; Leak detection; Spectroscopy; Sulfur hexafluoride; Temperature; PA cell; SF6 gas; leakage detection; photoacoustic spectrometry;
fLanguage
English
Publisher
ieee
Conference_Titel
Measuring Technology and Mechatronics Automation, 2009. ICMTMA '09. International Conference on
Conference_Location
Zhangjiajie, Hunan
Print_ISBN
978-0-7695-3583-8
Type
conf
DOI
10.1109/ICMTMA.2009.148
Filename
5202962