• DocumentCode
    2943936
  • Title

    A method for calibration of partial discharge calibrators

  • Author

    Gunnarsson, O. ; Bergman, A. ; Rydler, K.-E.

  • Author_Institution
    Swedish Nat. Testing & Res. Inst., Boras, Sweden
  • fYear
    1998
  • fDate
    6-10 July 1998
  • Firstpage
    205
  • Lastpage
    206
  • Abstract
    A method for calibration of partial discharge calibrators has been developed based on passive integration of the induced charge. The voltage over a known capacitor is measured by a calibrated digital sampling voltmeter and the charge is calculated as the voltage multiplied by the capacitance. The best achieved uncertainty is /spl plusmn/2% for a coverage factor k=2.
  • Keywords
    calibration; digital voltmeters; partial discharge measurement; calibration; capacitance; coverage factor; digital sampling voltmeter; induced charge; partial discharge calibrator; passive integration; uncertainty; Calibration; Capacitance measurement; Capacitors; Charge measurement; Current measurement; Partial discharge measurement; Partial discharges; Sampling methods; Voltage; Voltmeters;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements Digest, 1998 Conference on
  • Conference_Location
    Washington, DC, USA
  • Print_ISBN
    0-7803-5018-9
  • Type

    conf

  • DOI
    10.1109/CPEM.1998.699868
  • Filename
    699868