DocumentCode
2946595
Title
Time domain PD-detection vs. dielectric spectroscopy
Author
Holbøll, J.T. ; Gäfvert, U. ; Edin, H.
Author_Institution
Dept. of Electr. Power Eng., Tech. Univ., Lyngby, Denmark
Volume
2
fYear
1997
fDate
19-22, Oct 1997
Firstpage
498
Abstract
A theoretically developed relationship between partial discharges and the response from a system for dielectric spectroscopy was experimentally confirmed. The losses caused by the discharges were highest at test voltages with low frequencies. At 0.1 Hz, tanδ tip-up at discharge inception was very difficult to observe. A very clear tip-up could be seen by detection of the third harmonic in the current through the test object. This is much more sensitive to the detection of internal partial discharges than traditional loss measurements, in particular when using low frequency test voltages
Keywords
charge measurement; dielectric loss measurement; insulation testing; partial discharges; time-domain analysis; 0.1 Hz; current third harmonic; dielectric spectroscopy; discharge inception; insulation diagnostic tools; internal partial discharges; losses; low frequency test voltages; tanδ tip-up; time domain PD-detection; Capacitance; Dielectric losses; Dielectric measurements; Dielectrics and electrical insulation; Electrochemical impedance spectroscopy; Electrodes; Frequency; Partial discharges; Power engineering and energy; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 1997. IEEE 1997 Annual Report., Conference on
Conference_Location
Minneapolis, MN
Print_ISBN
0-7803-3851-0
Type
conf
DOI
10.1109/CEIDP.1997.641120
Filename
641120
Link To Document