  • Abstract
    The paper presents a load model to assess the voltage stability margin of power system with a large share of air conditioning (AC) load. The first part of the paper describes the laboratory tests performed on a set of electrical appliances and the dedicated load monitoring campaign performed in the power system of Dubai (UAE). It illustrates the non linear nature of the load following large disturbances. The second part of the paper presents a general methodological approach to model at system level the distributed undervoltage relays embedded in the electrical AC appliances single and three phase LV connected and MV connected appliances.
  • Keywords
    air conditioning; condition monitoring; domestic appliances; load shedding; power system stability; AC load; MV connected appliance; electrical appliance; laboratory staged testing; load model development; load monitoring campaign; power system; three phase LV connected appliance; voltage stability; Home appliances; Induction motors; Load modeling; Monitoring; Power system dynamics; Voltage fluctuations; Load modeling; air conditioning; load shedding; rotating load; voltage stability;