• DocumentCode
    3008936
  • Title

    Application of MV GIS partial discharge measurement and location

  • Author

    Min-Yen Chiu ; Keng-Wei Liang ; Chang-Hsing Lee ; Chen-Li Fan ; Cheng, James ; Lin Yu-Chih

  • Author_Institution
    Power Diagnostic Service Co., Ltd., Hsinchu, Taiwan
  • fYear
    2012
  • fDate
    23-27 Sept. 2012
  • Firstpage
    462
  • Lastpage
    465
  • Abstract
    While the demand of electric power increases and the installation space of power equipment is fixed in a factory, the gas insulated switchgear (GIS) is gradually applied to medium voltage system due to its small size and easy maintenance. However, it also takes longer time for the repair of GIS accident. Therefore, the preventive maintenance (PDM) is very important and the most effective method is partial discharge measurement. Unfortunately, the metal-cladded GIS usually makes PDM inconvenient, especially for the partial discharge location. This paper provides a fast and easy method for the location of partial discharge in GIS, it can locate the defect quickly and effectively, and the related strategy can be made in advance.
  • Keywords
    gas insulated switchgear; partial discharge measurement; preventive maintenance; GIS accident; MV GIS partial discharge measurement; PDM; electric power demand; gas insulated switchgear; medium voltage system; metal-cladded GIS; partial discharge location; power equipment; preventive maintenance; Correlation coefficient; Delay effects; Gas insulation; Maintenance engineering; Partial discharge measurement; Partial discharges; Position measurement; Correlation Coefficient; Gas Insulated Switchgear; Partial Discharge;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
  • Conference_Location
    Bali
  • Print_ISBN
    978-1-4673-1019-2
  • Type

    conf

  • DOI
    10.1109/CMD.2012.6416179
  • Filename
    6416179