• DocumentCode
    3009332
  • Title

    On-line partial discharge monitoring system for distribution networks

  • Author

    Mulroy, Patrick ; Hurtado, A. ; Badetz, D.

  • Author_Institution
    Ormazabal Corp. Technol., Amorebieta-Etxano, Spain
  • fYear
    2012
  • fDate
    23-27 Sept. 2012
  • Firstpage
    542
  • Lastpage
    545
  • Abstract
    Partial discharges (PD) occur as a result of dielectric breakdown in electrical insulation under high voltage stress. PD activity, once initiated, causes chemical and physical degradation of insulating material and can lead to catastrophic failure. Early warning of PD activity and localisation is considered essential to ensure the reliable operation over the long term of high voltage equipment including cables, cable accessories and switchgear. PD detection in high voltage cable and cable accessories is usually carried out with test objects offline, requiring potentially significant interruption of service. An online detection system is preferable but difficult to calibrate apparent charge magnitudes due to changes in real distribution network loading and topologies. An online PD detection system with continuous calibration has been developed to determine the apparent charge magnitudes of PD activity and locations in a section of in-service distribution network with high monitoring frequency and no requirement to take cables off line. Results of the on-line PD monitoring system in a typical urban distribution network in Spain are presented. System components including the online calibration pulse injector, capacitive sensors for high frequency PD pulse detection, and data acquisition, processing and communication components at each monitoring site are presented.
  • Keywords
    distribution networks; electric breakdown; insulating materials; partial discharges; switchgear insulation; PD activity; Spain; cable accessories; capacitive sensors; catastrophic failure; dielectric breakdown; distribution network loading; electrical insulation; insulating material degradation; on-line partial discharge monitoring system; online PD detection system; online calibration pulse injector; reliable operation; service distribution network; switchgear; urban distribution network; Calibration; Monitoring; Partial discharges; Phase frequency detector; Power cable insulation; Power cables; PD detection; distribution network; online calibration; online monitoring; partial discharges;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
  • Conference_Location
    Bali
  • Print_ISBN
    978-1-4673-1019-2
  • Type

    conf

  • DOI
    10.1109/CMD.2012.6416200
  • Filename
    6416200