DocumentCode
3010190
Title
Power cable joint modelin high frequency
Author
Yan Li ; Wouters, P.A.A.F. ; Wagenaars, P. ; van der Wielen, P.C.J.M. ; Steennis, E.F.
Author_Institution
Electr. Energy Syst., Eindhoven Univ. of Technol., Eindhoven, Netherlands
fYear
2012
fDate
23-27 Sept. 2012
Firstpage
76
Lastpage
79
Abstract
Models in high frequency range for underground power cabling system are the basis for the analysis of many condition diagnostic techniques, for instance, partial discharge (PD) monitoring. This paper focuses on modeling of power cable joints. A cascaded transmission line model is proposed for 10kV oil-filled PILC-PILC straight power cable joint in the frequency range of 300 kHz-800 MHz. It can be applied to interpret PD signal transmission and reflection behavior in power cable connections. The model is verified by S-parameter measurement.
Keywords
S-parameters; paper; partial discharges; power cables; power transmission lines; underground cables; PD signal transmission; S-parameter measurement; cascaded transmission line; frequency 300 kHz to 800 MHz; high frequency range; many condition diagnostic techniques; oil-filled PILC-PILC straight power cable joint; paper-insulated lead-covered cable; partial discharge monitoring; power cable connections; reflection behavior; underground power cabling system; voltage 10 kV; Frequency measurement; Joints; Oil filled cables; Power cables; Scattering parameters; Transmission line measurements; monitoring; parameter estimation; partial discharges; power cable insulation; transmission lines;
fLanguage
English
Publisher
ieee
Conference_Titel
Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
Conference_Location
Bali
Print_ISBN
978-1-4673-1019-2
Type
conf
DOI
10.1109/CMD.2012.6416243
Filename
6416243
Link To Document