DocumentCode
3011567
Title
Statistical analysis of partial discharge characteristics for predictive maintenance of generator of geothermal power plant
Author
Darwanto, Djoko ; Hamdani, Deny ; Hariyanto, D.D. ; Karyawan, O.H.
Author_Institution
Sch. of Electr. Eng. & Inf., Inst. Teknol. Bandung, Bandung, Indonesia
fYear
2012
fDate
23-27 Sept. 2012
Firstpage
1003
Lastpage
1006
Abstract
In order to guarantee reliable industrial power supply, predictive maintenance for generator becomes highly necessary. This measure is expected to reduce disruptive generator due to degraded insulation of its stator winding. Partial discharge (PD) is responsible for this disadvantage condition. The objective of this paper is present partial discharge (PD) analysis using statistical methods for predictive maintenance of generator in geothermal power plant. TGA-B IRIS was used for online PD measurement. The measurement data is analysed statistically to forecast the time of critical condition of stator winding of generator using vector autoregressive (VAR) method. The analysis result became the basis of predictive maintenance.
Keywords
autoregressive processes; geothermal power stations; maintenance engineering; partial discharge measurement; power generation reliability; statistical analysis; stators; TGA-B IRIS; geothermal power plant; online PD measurement; partial discharge analysis; predictive maintenance; statistical analysis; stator winding; vector autoregressive method; Correlation; Generators; Insulation; Iris; Partial discharges; Reactive power; Stator windings; goethermal; insulation; partial discharge; predictive maintenance; vector autoregressive;
fLanguage
English
Publisher
ieee
Conference_Titel
Condition Monitoring and Diagnosis (CMD), 2012 International Conference on
Conference_Location
Bali
Print_ISBN
978-1-4673-1019-2
Type
conf
DOI
10.1109/CMD.2012.6416325
Filename
6416325
Link To Document