DocumentCode
3082836
Title
Grounding fault protection in distribution system based on method of the module maximum value
Author
Xiao Bai ; Yan Hao ; Li Guang-yu ; Bai Yang
Author_Institution
North China Electr. Power Univ., Baoding, China
fYear
2008
fDate
10-13 Dec. 2008
Firstpage
1
Lastpage
5
Abstract
Fault line detection in distribution system is a problem. In this paper, method of the module maximum value is employed to analyze the electric information after the fault, and to respond the abrupt change of zero sequence currents, and through comparing the change of the zero sequence currents on all lines´ polarities and magnitudes, then the fault line can be determined. With the using of inner product, the criterion has good property of containing error, and so that it can get more high precision of fault line detection. This method is suited for various distribution systems with different neutral grounding modes. Moreover, it can be easily used in site without adjusting protective setting. EMTP simulations show that the method is effective and reliable.
Keywords
earthing; fault currents; fault diagnosis; power distribution faults; power distribution lines; power distribution protection; EMTP simulation; distribution system; electric information analysis; fault line detection; grounding fault protection; module maximum value; neutral grounding modes; zero sequence currents; Circuit faults; Cities and towns; EMTP; Electrical fault detection; Fault detection; Grounding; Information analysis; Power supplies; Power system protection; Voltage; Distribution system; Fault line detection; Singular detection; Wavelets transform;
fLanguage
English
Publisher
ieee
Conference_Titel
Electricity Distribution, 2008. CICED 2008. China International Conference on
Conference_Location
Guangzhou
Print_ISBN
978-1-4244-3373-5
Electronic_ISBN
978-1-4244-3372-8
Type
conf
DOI
10.1109/CICED.2008.5211755
Filename
5211755
Link To Document