• DocumentCode
    3094454
  • Title

    Rotor Current Controller with Voltage Harmonics Compensation for a DFIG Operating under Unbalanced and Distorted Stator Voltage

  • Author

    Ramos, C.J. ; Martins, A.P. ; Carvalho, A.S.

  • Author_Institution
    Univ. do Porto, Porto
  • fYear
    2007
  • fDate
    5-8 Nov. 2007
  • Firstpage
    1287
  • Lastpage
    1292
  • Abstract
    The doubly fed induction generator is particularly appropriate to be used in wind power generation systems. However, in weak grids its stator connection to unbalanced or distorted voltages imposes low frequency and high amplitude rotor current harmonics. Also, the grid side converter must deal with the same voltage conditions. The paper addresses the first issue presenting a voltage harmonics controller in the dq reference frame to be included in the high dynamics rotor current controller. Simulation and experimental results demonstrate the performance of the proposed controller imposing a sinusoidal input current.
  • Keywords
    asynchronous generators; compensation; electric current control; machine control; power conversion harmonics; power grids; rotors; DFIG; doubly fed induction generator; dq reference frame; grid side converter; rotor current controller; unbalanced distorted stator voltage; voltage harmonics compensation; wind power generation system; Control systems; Harmonic distortion; Induction generators; Machine vector control; Power system modeling; Rotors; Stators; Voltage control; Wind energy; Wind turbines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics Society, 2007. IECON 2007. 33rd Annual Conference of the IEEE
  • Conference_Location
    Taipei
  • ISSN
    1553-572X
  • Print_ISBN
    1-4244-0783-4
  • Type

    conf

  • DOI
    10.1109/IECON.2007.4459938
  • Filename
    4459938