DocumentCode
3101148
Title
Hydro one distribution voltage performance design criteria and power distance test in enabling distributed generation
Author
Tang, Lianxiang ; Yan, Andrew ; Marti, Luis ; Fuerth, John
Author_Institution
Hydro One Networks Inc., Toronto, ON, Canada
fYear
2012
fDate
7-10 May 2012
Firstpage
1
Lastpage
8
Abstract
Voltage performance has become a sensitive issue since Hydro One began to integrate a large amount of Distributed Generation (DG) in its distribution system. With the advent of the Feed-In Tariff (FIT) program, Hydro One has established a set of voltage performance design criteria to be used in DG Customer Impact Assessment (CIA). Governed by the voltage performance design criteria, a methodology was developed in order to accommodate a high level of DG penetration without an Advanced Distribution System (ADS). The methodology gives rise to a simple Power Distance Test (PDT) used for the purpose of voltage performance assessment.
Keywords
distributed power generation; fluctuations; tariffs; voltage control; voltage distribution; ADS; DG CIA; DG customer impact assessment; DG penetration; FIT program; PDT; advanced distribution system; distributed generation; distribution system; feed-in tariff program; hydro one distribution voltage performance design; power distance test; Capacitors; Fluctuations; Low voltage; Reactive power; Regulators; Voltage control; Voltage fluctuations; Distributed Generation; Voltage Fluctuation; Voltage Regulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exposition (T&D), 2012 IEEE PES
Conference_Location
Orlando, FL
ISSN
2160-8555
Print_ISBN
978-1-4673-1934-8
Electronic_ISBN
2160-8555
Type
conf
DOI
10.1109/TDC.2012.6281417
Filename
6281417