DocumentCode
3120003
Title
Insulation performance under switched voltage waveforms
Author
Hains, A.J.
fYear
1999
fDate
1999
Firstpage
42401
Lastpage
42405
Abstract
The increasing use of IGBT-controlled pulse width modulated voltage waveforms for motor power supplies has prompted many studies to evaluate their impact upon insulation system performance. The works described in this paper indicate that when voltage waveforms contain significant harmonics at frequencies close to the relaxation peak for the insulation, failure arising from surface charge accumulation can occur. Ageing by partial discharges will take place when the voltage is above the discharge inception level and this level may change according to the duty cycle of individual carrier periods. If operating conditions do not promote either of these mechanisms, failure will occur through normal thermal degradation
fLanguage
English
Publisher
iet
Conference_Titel
Effects of High Speed Switching on Motors and Drives (Ref. No. 1999/144), IEE Colloquium on
Conference_Location
Birmingham
Type
conf
DOI
10.1049/ic:19990733